Skip to content

Coolant Check Valve and Relief Valve Guide for Deep Hole Drilling

Check valves and relief valves are small components with big responsibilities. A failed check valve allows chips to flow backward into the pump. A failed relief valve can allow pressure to exceed hose rating, causing a violent hose burst. These valves must be selected correctly, tested regularly, and replaced on schedule.

Check Valve Types

Check Valve Comparison

TypeMechanismPressure RangeFlow RangeCrack PressureApplication
Spring-loaded (poppet)Spring pushes poppet onto seat10–350 bar5–200 L/min0.1–1.0 barGeneral coolant system — most common
Spring-loaded (ball)Spring pushes ball onto seat10–200 bar5–100 L/min0.5–3.0 barSmall bore applications
Pilot-operatedPilot pressure opens main poppet10–350 bar20–500 L/minVariableHigh-flow circuits, accumulator isolation
Swing-typeHinged disc swings open with flow2–50 bar50–1,000 L/minVery low (< 0.1 bar)Low-pressure high-flow return lines

Check Valve Selection

ApplicationRecommended TypeWhy
Pump outlet (high pressure)Spring-loaded poppetReliable sealing at high pressure
Coolant line to drillSpring-loaded poppetPrevents chip backflow
Return line from machineSwing-type or spring-loadedLow pressure drop
Accumulator isolationPilot-operatedControlled opening, high flow
Bypass lineSpring-loaded ballCompact, simple
Coolant collar supplySpring-loaded poppetPositive seal when not drilling

Check Valve Failure Modes

FailureSymptomCauseCorrective Action
Leaking (passing reverse flow)Pressure drops when pump stops, chips in pumpSeat wear, poppet damage, contamination on seatClean or replace valve
Stuck closedNo flow in forward directionContamination jamming poppet, corrosionClean or replace valve
Stuck openReverse flow continuesBroken spring, poppet jammed openReplace valve
Chatter (rapid open/close)Noise, pressure fluctuationFlow too low for valve size, wrong springReplace with correctly sized valve
External leakageCoolant visible at valve bodySeal/ O-ring failure, cracked bodyReplace seals or valve

Relief Valve Types

Relief Valve Comparison

TypeMechanismPressure RangeFlow CapacityResponse TimeApplication
Direct-acting (poppet)Spring force directly opposes poppet10–200 barLow to moderateFast (< 10 ms)Simple overpressure protection
Direct-acting (ball)Spring force directly opposes ball10–100 barLowFastLow-cost protection
Pilot-operatedSmall pilot valve controls main valve20–350 barHighModerate (20–50 ms)High-flow systems, accurate pressure control
ProportionalElectronic control of pressure setting10–300 barModerate to highModerateVariable pressure applications

Relief Valve Selection

ApplicationRecommended TypeWhy
Coolant pump outlet (primary protection)Direct-acting or pilot-operatedFast response, reliable
High-pressure coolant circuitPilot-operatedAccurate pressure control at high flow
Low-pressure return circuitDirect-actingSimple, low cost
Accumulator circuitPilot-operatedPrevents spurious opening from pressure spikes
Coolant collar supplyDirect-actingFast response protects seals
Bypass filtration circuitDirect-actingLow flow, simple protection

Relief Valve Failure Modes

FailureSymptomCauseCorrective Action
Stuck open (blowing continuously)Low/zero system pressure, hot coolantContamination on seat, spring brokenClean or replace valve
Stuck closed (no relief)Pressure exceeds setpoint, potential hose burstCorrosion, contamination jammingReplace valve immediately
Drift (setting changes)Pressure gradually changesSpring fatigue, seat wearRe-set or replace valve
ChatterRapid valve cycling, noiseFlow too high for valve capacity, unstable systemCheck system design, replace with correctly sized valve
External leakageCoolant visible at adjustment screw or bodySeal failure, cracked bodyReplace seals or valve

Valve Setting Procedures

Relief Valve Setting

StepActionDetail
1Install accurate pressure gauge at valveUse gauge with range 1.5× expected setting
2Ensure system is at operating temperatureCold coolant changes viscosity and pressure readings
3Close isolation valve downstream of relief (if safe)Or block system to create dead-head condition
4Start pump at low speedIncrease speed while monitoring pressure
5Observe pressure at which valve opensPressure stabilizes at the relief setting
6Adjust valve: turn screw IN to increase, OUT to decreaseSmall adjustments — 1/8 turn at a time
7Re-test after adjustmentAllow pressure to stabilize
8Set at 110% of maximum operating pressureMargin prevents nuisance opening
9Lock adjustment screwSecure with locknut or seal wire
10Record settingDate, pressure, valve ID, operator

Check Valve Testing

StepActionDetail
1Isolate check valve from systemClose upstream and downstream isolation valves
2Apply pressure in reverse directionUse hand pump or system pressure
3Observe pressure gaugePressure should hold — any drop indicates leakage
4Apply pressure in forward directionValve should open at crack pressure
5Measure crack pressurePressure at which flow begins
6Compare to specificationReplace if crack pressure is > 20% above spec
7Record resultsDate, crack pressure, leakage, valve ID

Installation Best Practices

Check Valve Installation

PracticeReasonImplementation
Install with flow arrow pointing downstreamPrevents reverse installationVerify arrow direction before installation
Install vertically (vertical pipe) with flow upwardGravity assists closingPreferred orientation — reduces wear
Install horizontally only if necessaryHorizontal may allow disc to hang openUse spring-loaded type for horizontal
Provide straight pipe before valve (5× pipe diameter)Reduces flow turbulence that affects operationStraight pipe run upstream
Install isolation valves around check valveEnables removal for testing without draining systemBall valves upstream and downstream

Relief Valve Installation

PracticeReasonImplementation
Install as close to pressure source as possibleFaster response to overpressureWithin 1 m of pump outlet
Install tee-style with branch to reliefFlow enters side, relief is on branchPrevents debris from settling on seat
Provide straight pipe before valveReduces turbulence effects on setting5× pipe diameter minimum
Never install isolation valve between pump and reliefIsolation defeats the safety functionRelief must always be connected
Route relief return to tank or low-pressure areaDischarge must go somewhere safeVisible discharge line
Support valve and discharge pipingPrevents pipe stress from affecting settingPipe clamps, valve bracket

Common Valve Problems

ProblemLikely CauseDiagnostic CheckCorrective Action
Relief valve opens below set pressureSpring weakened, wrong spring installedRemove and test spring forceReplace spring
Relief valve does not close after openingContamination on seat, poppet damagedRemove and inspect seat and poppetClean or replace
Check valve leaks in reverse directionSeat wear, contamination, spring brokenPressure test in reverseClean or replace
Valve body cracksOverpressure, freeze damage, fatigueVisual inspectionReplace valve — repair not possible
Valve corrodes internallyWrong material for coolant chemistryInspect during maintenanceUpgrade to stainless steel
Chatter under normal operationValve oversized, system instabilityCheck flow rate vs valve ratingInstall correctly sized valve

Maintenance Schedule

ComponentWeeklyMonthlyQuarterlyAnnually
Check valve (spring-loaded)Function testReplace or rebuild
Check valve (swing-type)Visual check of hingeReplace if worn
Relief valve (direct-acting)Verify settingRebuild or replace
Relief valve (pilot-operated)Verify settingRebuild or replace
All valve sealsVisual for leakageReplace
All valve bodiesVisual for cracksReplace if damaged

FAQ

What is the purpose of a check valve in a deep hole drilling coolant system?

The check valve prevents reverse flow when the coolant pump stops. Without a check valve at the pump outlet, chips and coolant from the machine can flow backward through the supply line and into the pump when the pump stops. Chips entering a piston pump cause immediate scoring of the valve plate and pistons. The check valve also maintains pressure in the supply line, preventing air from entering when the system is off.

What is the purpose of a relief valve in a deep hole drilling coolant system?

The relief valve limits maximum system pressure to prevent overpressure damage. If a coolant line becomes blocked (closed valve, clogged drill, chip jam), the pump continues to generate pressure until something fails — a hose bursts, a seal blows, or the pump is damaged. The relief valve opens at a set pressure (typically 110% of maximum operating pressure) and diverts flow back to the tank, preventing the pressure from exceeding safe limits.

How do I set the relief valve on a deep hole drilling coolant system?

Set the relief valve at 110% of the maximum normal operating pressure. To set: install an accurate pressure gauge at the valve, start the pump, gradually increase pressure until the valve opens (pressure stabilizes), adjust the valve screw (IN to increase, OUT to decrease), re-test, and lock the adjustment. For a system operating at 100 bar, set the relief valve at 110 bar.

What causes a relief valve to chatter?

Chatter (rapid opening and closing) is caused by: the valve being oversized for the flow rate (flow is too low to keep the valve stably open), system pressure instability (pump pulsation, other valves cycling), or incorrect spring selection. Chatter causes rapid wear of the seat and poppet. Fix by sizing the relief valve to match the actual system flow, not the pump maximum flow.

How often should coolant system valves be tested?

Check valves: function test quarterly — apply pressure in the reverse direction and verify the valve holds. Relief valves: verify setting monthly — observe the pressure at which the valve opens. Rebuild or replace both valve types annually or whenever they fail testing. For critical systems (high pressure > 100 bar, or safety-related applications), increase testing frequency to monthly for check valves and weekly for relief valves.


Check valves and relief valves are the unsung safety components of a deep hole drilling coolant system. A properly functioning check valve keeps chips out of the pump. A properly set relief valve prevents overpressure failures. Test them regularly, replace them on schedule, and never bypass or disable them. This article reflects industry practice as of 2026.

Deep Hole Drilling Hub — Your Trusted Third-Party Industry Resource