Skip to content

Coolant Tank Level Sensor Calibration for Deep Hole Drilling

A coolant tank level sensor that does not alarm when the tank is low is the same as having no level sensor at all — except that everyone believes the machine is protected. An uncalibrated sensor creates a false sense of security that can lead to pump damage and production interruptions.

Level Sensor Types

Sensor Comparison

Sensor TypeOperating PrincipleAccuracyCostApplicationContamination Sensitivity
Float switch (mechanical)Float rises and falls with coolant level — activates switch at set point± 5 mmLowLow-level alarm, fill controlModerate — float can stick
Conductivity (probe)Two electrodes — circuit completes when coolant contacts both± 10 mmLowLow-level alarmLow — coolant must be conductive
UltrasonicSound wave reflects from coolant surface — measures distance± 2 mmModerateContinuous level monitoringModerate — foam, mist affect reading
Pressure (hydrostatic)Pressure sensor at tank bottom — pressure proportional to height± 3 mmModerateContinuous level monitoringLow — self-cleaning
CapacitanceDielectric change between sensor and coolant surface± 3 mmHighContinuous — harsh environmentsLow — affected by coolant type change
RadarMicrowave reflects from coolant surface± 1 mmHighPrecision continuous levelLow — unaffected by foam, mist

Sensor Selection by Tank Type

Tank TypeRecommended SensorWhy
Chip tank (large, open)Ultrasonic or pressureHandles large tanks, tolerant of contamination
Coolant supply tank (closed)Float switch or conductivitySimple, reliable, low cost
High-pressure pump tankPressure or conductivityCompact installation, reliable
Bypass / kidney loop tankFloat switchSmall tank, simple alarm
Temperature-controlled tankUltrasonic or pressureContinuous monitoring for chiller control

Calibration Procedures

Float Switch Calibration

StepActionDetail
1Identify float switch typeNormally open (NO) or normally closed (NC)
2Verify float moves freelyNo binding, no accumulated debris
3Determine set pointTypically 20–30% of tank height for low-level alarm
4Drain tank to set point levelMark the level on the tank exterior
5Adjust float switch positionSlide switch up or down on mounting bracket
6Test at set pointFloat should activate switch at marked level
7Test above set pointSwitch should de-activate
8Test below set pointSwitch should activate
9Secure switch positionTighten mounting bracket
10Document calibrationSet point level, date, operator

Conductivity Probe Calibration

StepActionDetail
1Clean probe tipsRemove any coating or residue
2Set probe lengthCut or extend probe to reach desired set point level
3Fill tank above probe tipVerify circuit closes (conductivity detected)
4Drain tank below probe tipVerify circuit opens (no conductivity)
5Adjust sensitivity (if electronic controller)Set per manufacturer specification
6Test with actual coolantNot water — coolant has different conductivity
7Document calibrationProbe length, set point, date

Ultrasonic Sensor Calibration

StepActionDetail
1Clean sensor faceRemove any coolant residue or debris
2Enter tank dimensions in controllerTank height, shape (cylindrical or rectangular)
3Set empty level (4 mA or 0%)Tank empty — reference point
4Set full level (20 mA or 100%)Tank full — reference point
5Set alarm thresholdsTypically 20% for low-level alarm
6Set damping / averagingPrevents false alarms from surface turbulence
7Test at emptyVerify 4 mA output or 0% reading
8Test at known levelFill to measured height, verify sensor reading
9Adjust if neededOffset or span adjustment per manufacturer
10Document calibrationEmpty, full, alarm settings, date

Pressure Sensor Calibration

StepActionDetail
1Verify sensor is at tank bottomClean sensor diaphragm
2Ensure sensor port is clearNo debris blocking diaphragm
3Set zero (tank empty)Sensor should read 0 bar / 4 mA
4Fill tank to known heightMeasure height with tape or rod
5Compare sensor reading to calculated pressurePressure (bar) = height (m) × density (kg/L) × 0.0981
6Adjust span if neededPer manufacturer calibration procedure
7Test at multiple levels25%, 50%, 75%, 100%
8Set alarm thresholdsTypically 20% low-level, 95% high-level
9Document calibrationHeight vs pressure readings, date

Installation Considerations

Sensor Location

Sensor TypeOptimal LocationAvoid
Float switchAway from fill inlet and return linesTurbulent areas, near pump suction
Conductivity probeVertical or near vertical in still zoneAreas with foam, near agitation
UltrasonicTop of tank — clear path to coolant surfaceFoam accumulation area, fill inlet
PressureTank bottom — in stilling well if possibleNear pump suction, near return line
CapacitanceSide-mounted or top-mounted per typeAreas with heavy buildup

Stilling Well Installation

BenefitHow It WorksWhen to Use
Isolates sensor from turbulenceVertical pipe with openings at bottom onlyUltrasonic and float sensors in agitated tanks
Prevents foam interferenceFoam cannot enter stilling wellUltrasonic sensors in foaming coolant
Protects sensor from debrisDebris settles below stilling well intakePressure sensors on bottom
Provides consistent measurement pointFixed cross-section, known geometryAll continuous level sensors

Common Sensor Failures

FailureSymptomLikely CauseCorrective Action
False low-level alarmAlarm sounds when level is adequateFloat stuck, sensor contamination, foam triggeredClean sensor, check for foam
No alarm when lowPump runs dry — no alarmFloat sank, probe coated, sensor failedReplace sensor, verify alarm function weekly
Intermittent alarmAlarm comes and goesLoose wiring, connection corrosion, floating debrisCheck connections, clean tank
Erratic reading (continuous sensor)Level jumps 10%+ randomlyAir bubbles, foam on sensor, electrical noiseCheck installation, improve grounding
Reading driftLevel reading slowly changesSensor coating, temperature effectClean sensor, compensate for temperature
No signalController shows no readingSensor failed, wiring open, controller input failedReplace sensor, check wiring

Troubleshooting

No Alarm When Low

StepCheckIf Fails
1Is the sensor powered?Check power supply, wiring
2Does the sensor output change when level drops?Simulate low level — check output
3Is the alarm relay working?Check relay coil and contacts
4Is the PLC input working?Force input in PLC — verify signal reaches logic
5Is the alarm programmed correctly?Check PLC program logic

False Alarm

StepCheckIf Fails
1Is the coolant level actually low?Visual check of tank
2Is the sensor contaminated?Clean sensor
3Is there foam on the coolant surface?Check for foaming cause
4Is the sensor mounting loose?Tighten mounting
5Is the wiring intermittent?Check connections, wiggle test

Maintenance Schedule

Sensor TypeWeeklyMonthlyQuarterlyAnnually
Float switchVisual check of float movementFunctional test (drain to alarm level)Replace if > 3 years old
Conductivity probeClean probe tipsFunctional testReplace if corroded
UltrasonicClean sensor faceCheck reading at known levelFull calibration
Pressure sensorCheck zero readingFull calibration
CapacitanceClean sensor surfaceFunctional testFull calibration
All typesCheck wiring connections

FAQ

How do I calibrate a coolant level sensor on a deep hole drilling machine?

The calibration procedure depends on sensor type. For float switches: position the switch at the desired alarm level (typically 20–30% of tank height), verify it activates at that level, and secure it. For ultrasonic sensors: set empty and full references in the controller, set alarm thresholds, and verify readings at known levels. For pressure sensors: set zero at empty, verify pressure reading at a known fill height, and set alarm thresholds. Always document calibration results.

Why does my coolant level sensor give false low-level alarms?

False low-level alarms are most commonly caused by: foam on the coolant surface (ultrasonic sensors read the foam surface, which is higher than the liquid surface — then drops suddenly when foam collapses), contamination on the sensor (floating debris can trigger float switches), electrical noise (intermittent signals to the PLC), or sensor mounting that has loosened. Check the actual coolant level manually to confirm whether the alarm is real or false.

What type of level sensor works best for coolant tanks on deep hole drilling machines?

For simple low-level alarm: float switch or conductivity probe — reliable, low cost, easy to maintain. For continuous level monitoring: ultrasonic sensor (clean coolant) or pressure sensor (dirty coolant). Ultrasonic sensors are popular because they do not contact the coolant — eliminating contamination issues — but they can be fooled by foam and mist. Pressure sensors work well in dirty conditions but require periodic zero calibration.

How often should coolant level sensors be tested?

Test low-level alarms weekly: drain the coolant below the alarm set point and verify the alarm activates. This can be done by running the system in cycle while observing the alarm. For continuous level sensors, verify the reading against the actual tank level weekly. Perform a full calibration annually or whenever a sensor is replaced.

What happens if the coolant level sensor fails while drilling?

If the sensor fails to alarm when coolant level drops, the pump continues running with inadequate coolant supply. The pump may cavitate (causing noise and vibration), overheat, and damage internal components. In extreme cases, the pump runs dry and seizes. If the sensor fails in alarm state, the machine may not allow drilling to start — stopping production. Regular testing prevents both scenarios.


A coolant level sensor that has never been tested is not a safety device — it is a decoration. Test low-level alarms weekly, calibrate sensors annually, and never bypass a low-level alarm to continue production. A $100 sensor protects a $5,000 pump. This article reflects industry practice as of 2026.

Deep Hole Drilling Hub — Your Trusted Third-Party Industry Resource