Skip to content

Deep Hole Drilling Machine Coolant System Commissioning Guide

A deep hole drilling coolant system that is commissioned incorrectly can damage pumps within minutes, flood the shop floor within hours, and produce scrap holes for days before the root cause is identified. Commissioning is not a formality — it is the systematic verification that every component, from the tank to the drill, operates at its design specification. Following a structured commissioning sequence prevents startup failures and establishes baseline data for future condition monitoring.

Pre-Commissioning Checks

Mechanical Inspection

CheckDetailAcceptance Criteria
Piping integrityAll connections tight — no visible gapsNo leaks at any joint
Pipe slope (return lines)Verified with levelMinimum per pipe size table
Tank cleanlinessTank interior clean — no debris, no welding slagVisually clean — wipe test passes
Tank level sensorsFloat or ultrasonic — free movement — wiring connectedCorrect indication at empty/full
Pump alignmentCoupling alignment checked with dial indicator< 0.05 mm parallel — < 0.05 mm angular
Pump rotation directionMotor rotation checked (bump test)Matches arrow on pump housing
Filter housingsSeals in place — filter elements installedCorrect type and micron rating
ValvesAll valves in correct position (open/closed per startup checklist)Per startup checklist
Pressure gaugesInstalled — range appropriateCalibrated — readable
Flow metersInstalled — flow direction correctArrow matches flow direction
Heat exchanger / coolerConnections tight — coolant and utility connectionsNo leaks — correct flow paths
Mist collectorDuct connections sealed — filter installedProper connection to machine enclosure

Electrical Inspection

CheckDetailAcceptance Criteria
Motor wiringMotor connected to VFD or starter — correct phase rotationPhase rotation matches pump direction
VFD parametersSet per motor nameplateVoltage, frequency, current, ramp times
Pressure transducerWiring to PLC — signal type correct4–20 mA or 0–10 VDC per design
Flow meter wiringPulse or analog signal to PLCSignal type correct — no shorts
Level switch wiringNormally open or normally closed per safety circuitCorrect fail-safe configuration
Emergency stop circuitCoolant pump included in E-stopPump stops on E-stop activation
Alarm devicesHorn — light — PLC alarm inputFunction tested — audible and visual
Control panelAll terminals tight — no loose wiresTorque checked per specification

Pre-Fill Checks

CheckDetailAcceptance Criteria
Tank drain valveClosedNo leakage
Pump suction valveOpenFull flow to pump suction
Pump discharge valveInitially closed (for priming)Closed — will open after priming
Filter isolation valvesOpenFlow path through filters
Return line valvesOpenGravity flow path clear
Bypass valves (if equipped)Set to bypass initiallyCoolant recirculates to tank
Pressure relief valveSet to correct pressure10% above maximum operating pressure
All drain plugsTightenedNo leaks

Startup Sequence

Step-by-Step Startup

StepActionDetailExpected Result
1Fill tank with coolantMix per specification — fill to operating levelCorrect concentration — proper level
2Open pump suction valveFull openCoolant flows to pump inlet
3Prime the pumpFill pump housing with coolant — vent airNo air in pump housing
4Bump motor (momentary start)Check rotation directionCorrect rotation per pump arrow
5Start pump with discharge valve closedMinimum load startPump runs — no unusual noise
6Slowly open discharge valve10% increments — 30 seconds between stepsFlow increases smoothly — pressure builds
7Check for leaksAll joints — seals — fittingsNo leaks at any pressure
8Check pump suction pressureGauge at pump inletPositive suction pressure — no vacuum
9Check pump discharge pressureGauge at pump outletWithin design range
10Check flow rateFlow meterWithin design range
11Bleed air from systemAir vents at high pointsAll air purged
12Adjust pressure relief valveSet slightly above operating pressureCorrect setting verified
13Verify flow through all branchesEach machine or outletFlow at each outlet
14Check return line flowAt tank returnSmooth flow — no surging
15Run in recirculation mode30 minutes at operating conditionsStable temperature — stable pressure/no leaks

Pump Priming Methods

Pump TypePriming MethodDetail
Centrifugal (flooded suction)Open suction valve — coolant flows into pumpFill pump housing — no external prime needed
Centrifugal (suction lift)Fill pump housing through priming portMay need foot valve — vacuum pump for lifts > 3 m
Positive displacement (gear, piston)Fill pump housing through fill portNever run dry — even seconds of dry-run damages seals
Multistage centrifugalFlooded suction required — vent air at dischargeAir vent at highest point
Vertical turbineSubmerged in tank — no priming neededEnsure minimum submersion depth

Flushing Procedure

StepActionDetail
1Fill system with clean coolant (or flushing solution)Use fresh coolant — not production coolant
2Circulate at operating pressureFlow through all branches
3Open all valves — including bypass linesFlush all paths
4Run for 30–60 minutesRemoves construction debris — pipe dope — welding residue
5Check filter elements after flushingReplace if loaded with debris
6Sample coolant after flushingCheck for particles — debris
7If sample is clean — flush completeIf not — extend flush and replace filters again
8Drain flush coolant (or keep if clean enough)Per site procedure
9Fill with production coolantCorrect concentration — correct volume
10Final circulation — verify all parametersReady for production

Parameter Verification

Critical Parameters

ParameterVerification MethodAcceptance CriteriaAdjustment Method
Pump discharge pressurePressure gauge at pump outletWithin ± 5% of design pressurePressure relief valve — VFD speed
Flow rate (total)Flow meter at pump dischargeWithin ± 5% of design flowVFD speed — valve throttling (not preferred)
Flow rate (per machine)Flow meter at each machineWithin ± 10% of design per branchFlow control valve at each branch
Coolant temperatureTemperature gauge at tank20–30°C (or per specification)Chiller/heater setpoint adjustment
Coolant concentrationRefractometerPer coolant specificationAdd concentrate or water
Coolant pHpH meter8.5–9.5 (typical for water-soluble)Add pH adjuster per coolant spec
Filtration efficiencyParticle count before/after filter> 95% removal at rated micronCheck filter seal — element condition
Return line flowVisual — flow meter at tank returnSmooth continuous flowCheck slope — check for blockage

Temperature Control Verification

CheckMethodAcceptance
Cooler capacity testRun system at maximum heat load — measure temperature riseTemperature stabilizes within spec
Heater operation (if equipped)Activate heater — verify temperature riseHeater reaches setpoint within 30 minutes
Temperature controller responseStep change in setpoint — measure response timeStable within 5 minutes
Temperature sensor accuracyCompare to calibrated reference thermometer± 1°C

Safety System Verification

SystemTest MethodAcceptance
Low level shutdownDrain tank to low level switchPump stops — alarm sounds
High pressure reliefClose valve downstream — let pressure riseRelief valve opens at set pressure
Low flow alarmThrottle pump discharge — reduce flowAlarm at correct flow setpoint
Emergency stopPress E-stop buttonCoolant pump stops immediately
Mist collector interlockTurn off mist collectorMachine alarm — operator notification

Documentation

DocumentContentRetention
Commissioning checklistAll checks completed — signed offLife of machine
Parameter baseline recordAll measured parameters — date — operatorLife of machine
Pump test reportFlow vs pressure curve — amp drawLife of machine
Piping pressure test reportTest pressure — duration — leakageLife of machine
Flushing reportFlush duration — filter condition — sample results1 year
Coolant analysis (initial)Concentration — pH — bacteria — hardness1 year
As-built piping diagramRedline markups of design drawingsLife of machine

Common Commissioning Problems

ProblemLikely CauseCorrective Action
Pump will not primeSuction valve closed — air leak in suction lineOpen valve — check suction line gaskets
Low discharge pressurePump rotation wrong — suction restriction — worn pumpCheck rotation — clean suction strainer
High discharge pressure (low flow)Discharge valve closed — filter blocked — line restrictionOpen valve — check filters
Pump noisy (cavitation)Suction restriction — low tank level — viscous coolantClean suction strainer — check level — check coolant temperature
Coolant leaks at pipe jointsJoint not tightened — gasket damaged — pipe misalignedTighten — replace gasket — realign pipe
Return line floodingReturn line blocked — slope insufficient — tank return submergedClear blockage — improve slope — check tank level
Temperature not stableCooler undersized — bypass valve stuck — controller mis-setVerify cooler capacity — check bypass — tune controller
Flow rate below specificationPump speed too low — filter clogged — wrong impellerIncrease VFD speed — check filters — verify pump spec

FAQ

What is involved in commissioning a deep hole drilling coolant system?

Commissioning a coolant system involves: pre-commissioning checks (verify piping integrity, electrical connections, pump alignment, filter installation, and valve positions), filling and priming (fill tank with correctly mixed coolant, prime the pump to ensure no air in the housing), startup sequence (start pump with discharge valve closed, slowly open valve, verify pressure and flow at each stage), parameter verification (measure pressure, flow rate, temperature, concentration, and filtration efficiency at design conditions), flushing (circulate flushing fluid to remove construction debris), safety system testing (verify low level shutdown, pressure relief, low flow alarm, and emergency stop functions), and documentation (record all baseline parameters for future condition monitoring).

How do you prime a coolant pump on a deep hole drilling system?

Priming method depends on pump type: for a centrifugal pump with flooded suction (pump below tank level): simply open the suction valve — coolant flows into the pump housing and displaces air. For a centrifugal pump with suction lift (pump above tank level): fill the pump housing through the priming port — open the air vent on the pump discharge until coolant flows out without air bubbles. For positive displacement pumps: always fill the pump housing with coolant before starting — these pumps cannot tolerate dry running even for seconds. Never start a coolant pump without verifying it is primed — dry running damages mechanical seals within seconds.

What checks should be performed before starting a coolant pump?

Before starting a coolant pump: verify the tank is filled to the correct operating level with properly mixed coolant, open the pump suction valve fully (closed suction is the most common startup mistake), ensure the pump discharge valve is initially closed (opens slowly after start), check pump rotation direction by bumping the motor (must match arrow on pump housing — reverse rotation damages some pump types), verify all filter housings are sealed with elements installed, check all drain plugs are tight, and confirm the emergency stop circuit includes the pump. The single most important check is the suction valve — a pump started with a closed suction valve will cavitate immediately and can damage the seal within seconds.

How long does it take to commission a coolant system?

A typical coolant system commissioning for a deep hole drilling machine takes 1–2 days: pre-commissioning checks (2–4 hours — mechanical, electrical, pre-fill), startup and parameter verification (4–8 hours — filling, priming, startup, parameter adjustment), flushing (2–4 hours — depending on system volume and debris level), and safety system testing and documentation (2–4 hours — verify all safety functions, record baselines). Complex systems with multiple machines, temperature control, and advanced filtration may take 2–3 days. The most time-consuming step is usually flushing — if the piping system was not kept clean during installation, flushing can take significantly longer.

What baseline data should be recorded during commissioning?

Record the following baseline data during commissioning: pump discharge pressure and flow rate at operating conditions (at several VFD speeds if variable speed), coolant temperature at tank and at machine inlet (steady state values), amperage draw of the pump motor (at operating pressure and flow), all pressure readings across filters (clean filter pressure drop), vibration readings on pump and motor bearings, coolant concentration and pH, pressure relief valve setting, flow rate at each machine branch, and return line flow condition (visual — smooth, no surging). This baseline data is the reference for future condition monitoring — a 10% change from baseline indicates a developing problem.


Systematic coolant system commissioning prevents startup failures, establishes baseline data for condition monitoring, and verifies that every component operates at its design specification. Follow the pre-commissioning checks, startup sequence, parameter verification, and documentation steps to ensure the coolant system is ready for production. A well-commissioned coolant system starts reliably, operates efficiently, and provides years of trouble-free service. This article reflects industry practice as of 2026.

Deep Hole Drilling Hub — Your Trusted Third-Party Industry Resource